Publication Summary

Title

Snohomish Wastewater Treatment Plant Class II Inspection - September 20-21, 1992

Month-Year PublishedMarch 1993
Online Availability
View this publication in Acrobat PDF format
2441 kilobytes,  requires version 4.0 or later of Adobe Acrobat Reader Software  get Acrobat Reader
Short Description

A Class II Inspection was conducted in September 1992 at the city of Snohomish Wastewater Treatment Plant in Snohomish County. The Snohomish facility is a facultative lagoon system which discharges into the Snohomish River. The inspection data found the Snohomish facility was producing a fairly good effluent quality. Effluent concentrations were within the NPDES permit limitations with the exception of the monthly BOD5 average concentration. Flow was well within the design criteria specified in the permit, but BOD5 was approaching criteria.

(Also see abstract below)
Publication Number93-e59
Author(s)Stasch, P.
Print Availability
Request from the program.
Not maintained in stock. Copy must be made from archive version.
Number of pages 47 pp.
Keywords bioassay, BOD5, copper, county, effluent, flow, Inspection, metals, NPDES, priority pollutant, quality, river, silver, site investigation, Snohomish River, toxic, toxicity, treatment, waste, wastewater, wastewater treatment plant, water
Subject Waterbodies
Snohomish River
map of Washington state showing locations of subject waterbodies
Abstract Long Description

A Class II Inspection was conducted in September 1992 at the city of Snohomish Wastewater Treatment Plant in Snohomish County. The Snohomish facility is a facultative lagoon system which discharges into the Snohomish River. The inspection data found the Snohomish facility was producing a fairly good effluent quality. Effluent concentrations were within the NPDES permit limitations with the exception of the monthly BOD5 average concentration. Flow was well within the design criteria specified in the permit, but BOD5 was approaching criteria.

Effluent priority pollutant concentrations were generally less than the USEPA Quality Criteria for Water. Two metals, copper and silver, exceeded the freshwater chronic toxicity criteria by a small margin. The bioassays documented little toxicity in the effluent.